6.6.3 SENS - setting the sensor input
Select here whether the sensor is to send 4 - 20 mA or 0 - 10 V to the
controller for the actual value of the controlled variable (factory setting: 0 -
10 V).
Next enter the scaling. The range corresponding to the standard signal (4 -
20 mA or 0 - 10 V) is set, i.e. the pressure or flow rate or another type of
controlled variable is entered at 4 mA or 0 V (lower limit) and at 20 mA or 10
V (upper limit).
Settings between 0.000 and 9999 are possible. The unit corresponds to the value
set in the menu item UNIT .
(factory setting: S LO=0.00; S HI=10.00)
Example:
Lower limit ( S LO ) 2,5 bar
Upper limit ( S HI )
=> An actual value signal of 12 mA corresponds in this case to 11.25 bar
4 mA
20 bar
20 mA
8624-2 Standard - 23