4
TECHNICAL DATA
Operating voltage
Power consumption
Output current (to valve)
Operating temperature
Interference resistance
Interference emission
Inputs
1 setpoint input
1 actual value input
Resolution for both inputs
Input impedance (4 - 20 mA)
Input impedance (0 - 10 V)
Output
PWM output
Controller
Control algorithm
Scan time T
A
Amplification factor K
Reset time T
Scaling of controlled variable
Housing
Cable outlet
System of protection
Material
Dimensions (W x H x D)
Order no.
8 - 8624-2 Standard
P
N
24 V DC
max. 0,3 W (without proportional valve)
max. 1,0 A
- 10 ... + 60 °C
to EN50082-2
to EN50081-2
4 - 20 mA or 0 - 10 V, adjustable
4 - 20 mA or 0 - 10 V, adjustable
10 Bit
< 200 Ω
> 300 kΩ
24 V pulse width modulated
PI control
27 ms
0 - 10,00
0,05 - 200,1 s
0,000 - 9999
rotatable in 90° steps
IP 65
polyamide
54 x 54 x 61 mm
143 570