Télécharger Imprimer la page

Burkert 8695 Manuel D'utilisation page 51

Masquer les pouces Voir aussi pour 8695:

Publicité

Les langues disponibles

Les langues disponibles

Type 8695
DeviceNetinstallation
Procedure:
noTe!
Breakage of the pneumatic connection pieces due to rotational impact.
▶ When unscrewing and screwing in the transparent cap, do not hold the actuator of the process valve but the
connection housing.
Open the control head: turning the transparent cap anti-clockwise.
Figure 43:
Open control head
Set the DIP switches according to the following tables.
noTe!
Damage or malfunction due to penetration of dirt and humidity.
▶ To observe degree of protection IP65 / IP67, screw the transparent cap in all the way.
Close the device (assembly tool: 674078
Settings of the Devicenet address
MAC ID - Medium Access Control Identifier:
[DIP 1=off=0 / DIP 1=on=1 / MAC ID=DIP 1*2
Dip 1
Dip 2
[20=1]
[21=2]
off
off
on
off
off
on
...
...
off
on
on
on
Table 15:
Settings of the DeviceNet address
The assembly tool (674078) is available from your Bürkert sales office.
9)
All manuals and user guides at all-guides.com
Transparent cap
Body casing
Connection housing
Actuator
).
9)
+DIP 2*2
0
Dip 3
Dip 4
[22=4]
[23=8]
off
off
off
off
off
off
...
...
on
on
on
on
+...+DIP 6*2
]
1
5
Dip 5
Dip 6
[24=16]
[25=32]
off
off
off
off
off
off
...
...
on
on
on
on
english
mac iD
0
1
2
...
62
63
51

Publicité

loading