11.8
network topology of a Devicenet system
Line with a trunk line and several drop lines.
Trunk lines and drop lines consist of identical material (see "Figure 41").
V +
V –
CAN_H
CAN_L
Terminating
resistor
120 Ω
¼ W
Figure 41:
Network topology - DeviceNet
11.9
configuring the control head
11.9.1 Dip switches
Figure 42:
DIP switches - DeviceNet
8 DIP switches are available for configuration:
• DIP switches 1 to 6
• DIP switches 7 to 8
Danger!
risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
50
All manuals and user guides at all-guides.com
T01
Subscriber 1 (node 1)
1 2 3 4 5 6 7 8
OFF
for the DeviceNet address
for the baudrate
english
Type 8695
DeviceNetinstallation
Trunk line
DeviceNet cable
Drop lines
DeviceNet cable,
max. 6 m long
Terminating
resistor
120 Ω
¼ W
Tn
Subscriber n (node n)
DIP switches for
bus address and baudrate