Télécharger Imprimer la page

Burkert 8695 Manuel D'utilisation page 48

Masquer les pouces Voir aussi pour 8695:

Publicité

Les langues disponibles

Les langues disponibles

11.3.2 Drop line length
Baudrate
125 kbaud
250 kbaud
500 kbaud
Table 13:
Drop line length
11.4
safety setting if the bus fails
If the bus fails, the pilot valve is switched to a programmable safety setting (default: pilot valve isolated). For con-
figuration data see chapter entitled "11.9 Configuring the control head".
11.5
interfaces
Bus + supply
11.6
electrical connection Devicenet
The bus line is a 4-core cable with additional shielding which must conform to the DeviceNet specification.
The cable transmits both information (data) and energy (supply voltage for low-power actuators and sensors).
11.6.1 safety instructions
Danger!
risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.
Warning!
risk of injury from improper installation.
▶ Installation may be carried out by authorized technicians only and with the appropriate tools.
risk of injury from unintentional activation of the system and an uncontrolled restart.
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
48
All manuals and user guides at all-guides.com
length of the drop lines
maximum length
6 m for all baudrates
control head 8695
Devicenet
english
Type 8695
DeviceNetinstallation
maximum total length in the network
156 m
78 m
39 m
Bus