Télécharger Imprimer la page

Burkert 8695 Manuel D'utilisation page 52

Masquer les pouces Voir aussi pour 8695:

Publicité

Les langues disponibles

Les langues disponibles

Setting the baudrate
Adjusting the control head to the baudrate of the network.
Dip 7
off
on
off
on
Table 16:
Setting the baudrate
please note: if the settings are changed by actuating the Dip switches, this change will not take
effect until the device is restarted.
For a restart
• briefly disconnect the control head from the power supply and reconnect or
• switch the power supply off/on or
• transmit an appropriate reset message.
11.10 configuration of the process data
To transmit process data via an I/O connection, 1 static input and 1 static output assembly can be selected. These
assemblies contain selected attributes combined into one object so that process data can be transmitted collectively
via an I/O connection.
Process data can be accessed
• cyclically in the connection variants "Polled I/O" and "Bitstrobed I/O", with "Change of state", if input values
change, or
• acyclically via Explicit Messages.
The access path for acyclical access is:
With the Get_Attribute_Single service the input data can be accessed acyclically for reading.
With the Set_Attribute_Single service the output data can be accessed acyclically for writing.
1 data byte for inputs:
(sensors or initiators)
Bit
sensor
Bit 0
End position
Bit 1
End position
Bit 2... not used
Bit 7
Table 17:
data byte for inputs
52
All manuals and user guides at all-guides.com
Dip 8
Baudrate
off
125 kbaud
off
250 kbaud
on
500 kbaud
on
not permitted
Value assignment
0 Bot not reached
1 Bot reached
0 Top not reached
1 Top reached
0 always
english
class
4
instance 1
attribute 3
1 data byte for outputs:
(actuators or valves)
Bit
solenoid valve
Y1
Bit 0
Bit 1... not used
Bit 7
Table 18:
data byte for outputs
Type 8695
DeviceNetinstallation
Value assignment
0 Pilot valve
OFF
1 Pilot valve
ON
0 always

Publicité

loading