Télécharger Imprimer la page

Alliance Laundry Systems SWD448C Installation/Fonctionnement page 25

Publicité

Les langues disponibles

Les langues disponibles

Only flexible metal conduit, rigid metal conduit or
armored cable wiring systems are recommended.
Refer to Figure 17 for terminal block connections.
Electrical service for the dryer should be of maximium
rated voltage (208 or 240 Volt, depending on heating
element), listed on nameplate with a 40 Amp circuit
breaker or time delay fuse. Do not connect dryer to
110, 115 or 120 Volt circuit.
NOTE: Branch circuit wire size requirements are
shown in Table 4 .
Wire Length
Less than 15 ft. (4.5m)
Longer than 15 ft. (4.5m)
Table 4
Stacked Washers and Gas Dryers
(120 Volt, 60 Hertz, with Three-Prong Grounding
Plug)
NOTE: The wiring diagram is located behind the
control panel, inside the control cabinet.
WARNING
To reduce the risk of fire, electric shock or
personal injury, all wiring and grounding
MUST conform with the latest edition of the
National Electrical Code ANSI/NFPA 70 or
the Canadian Electrical Code, CSA C22.1,
and such local regulations as might apply. It
is the customer's responsibility to have the
wiring and fuses installed by a qualified
electrician to make sure adequate electrical
power is available to the dryer.
NOTE: Single electrical connection serves both
washer and dryer.
• The electric service must be a separate branch,
polarized, three-wire, effectively grounded, 120
Volt, 60 Hertz, AC (alternating current) circuit
protected by a 20 Ampere fuse, equivalent
fusetron or circuit breaker.
• The three-prong grounding plug on the power
cord should be plugged directly into a polarized
three-slot effectively grounded receptacle rated
120 Volts AC (alternating current) 20 Amps.
Refer to Figure 18 to determine correct polarity
of the wall receptacle.
802703
Wire
Listed No.8 AWG
Copper wire only
Listed No.6 AWG
Copper wire only
W516
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
1
115 ± 12
V.A.C.
5
STANDARD 120 VOLT, 60 HERTZ, 3-WIRE
EFFECTIVELY GROUNDED CIRCUIT
1
L1
2
Ground
3
Neutral
4
Round Grounding Prong
5
Neutral Side
Figure 18
NOTE: A qualified electrician should check the
polarity of the wall receptacles. If a voltage reading
is measured other than that illustrated, the
qualified electrician should correct the problem.
• DO NOT OPERATE OTHER APPLIANCES
ON THE SAME CIRCUIT WHEN THIS
APPLIANCE IS OPERATING. DO NOT
OVERLOAD CIRCUITS!
WARNING
To reduce the risk of an electric shock or
fire, DO NOT use an extension cord or an
adapter to connect the unit to the electrical
power source.
Installation
3
2
0
V.A.C.
115 ± 12
V.A.C.
4
D438i
D438I
W212
23

Publicité

loading