Installation
A
B
5
30°
1
NOTE: Where the exhaust duct pierces a
combustible wall or ceiling, the opening must be
sized per local codes.
2
Wall
2
3
1
CONNECT TO DRYER
5
VERTICAL EXHAUST INSTALLATION
1
Roof
2
No Screen or Cap
3
Wall
4
5 cm (2 in.) Minimum or Clearance Per Local
Codes
5
NOTE: Where the exhaust duct pierces a
combustible wall or ceiling, an opening must
be sized as shown or per local codes.
Figure 10
18
C
D
E
F
G
HORIZONTAL EXHAUST INSTALLATION
4
H319I
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
1
H
I
J
K
FLOW
EXHAUST AIR FLOW
MAXIMUM LENGTH OF DUCT
9.1 m (30 feet)
3
5 cm (2 in.) Minimum or Clearance per Local
Codes
4
No Screen or Cap
5
Clean Out Cover
Figure 9
To reduce the risk of fire and the
accumulation of combustion gases, DO NOT
exhaust dryer air into a window well, gas
vent, chimney or enclosed, unventilated
area, such as an attic, wall, ceiling, crawl
space under a building or concealed space
of a building.
Duct Station
A
B
C
D
E
F
G
H
I
J
K
A Backdraft Damper, Part No. 58786 (obtain locally),
should be installed in a 10.2 cm (4 inch) diameter
VERTICAL duct system. This will prevent a backdraft
when dryer is not in use, and will keep the exhaust air
in balance within the central exhaust system.
2
3
AIR
EXHAUST
OUTLET
Inspect Monthly
WARNING
Minimum Diameter of
Collector Duct
10.2 cm (4 inches)
20.3 cm (8 inches)
22.9 cm (9 inches)
25.4 cm (10 inches)
27.9 cm (11 inches)
30.5 cm (12 inches)
32.6 cm (13 inches)
35.6 cm (14 inches)
38.1 cm (15 inches)
38.1 cm (15 inches)
40.6 cm (16 inches)
4
H318I
W045
802703