• Dryer exhausts 220 cfm (measured at back of
dryer).
• DO NOT install flexible duct in concealed
spaces, such as a wall or ceiling.
• Static pressure in exhaust duct should not be
greater than 1.5 cm water column (.6 in.),
measured with manometer placed on exhaust
duct 61 cm (2 ft.) from dryer (check with dryer
running and no load). In multi-dryer installations,
all dryers connected to the main collector duct
should be operating when pressure is checked.
• Exhausting dryer in hard-to-reach locations can
be done by installing 521P3 Flexible Metal Vent
Kit (available as optional equipment at extra
cost).
• Sufficient make-up air must be supplied to
replace the air exhausted by the dryer. The free
area of any opening for outside air must be at
2
least 260 cm
(40 in
802703
2
).
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
• Energy efficient buildings with low air
infiltration rates should be equipped with an air
exchanger that can accommodate on demand
make-up air needs in the laundry room. These
devices can be obtained through your building
contractor or building material suppliers.
• Do not draw make-up air from a room containing
a gas fired water heater, a dry cleaner or a hair
salon.
• Failure to exhaust dryer properly will void
warranty.
NOTE: Venting materials are not supplied with the
dryer (obtain locally).
IMPORTANT: DO NOT block the airflow at the
bottom of the dryer's front panel with laundry,
rugs, etc. Blockage will decrease airflow through
the dryer, thus reducing the efficiency of the dryer.