If your installation is fitted with an automatic cutoff, this enables connection of
N1/L1 on the secondary circuit and N2/L2 on the main circuit.
Connect the earth to the external terminal of the unit provided for this
purpose.
Connect the power supply cable of your spa to 2 16A circuit breakers on
the electrical power supply panel.
A 30mA differential protection is to be scheduled if not already present, or
undersized on your home electrical power supply panel.
5.3. Differential system test
A monthly differential system test is essential. If the test does not function correctly, do
not power the electrical circuit and call an electrician as quickly as possible so that the
cause can be detected and repairs made if necessary.
Ensure that the general circuit breaker is set and that the spa is operating.
Press the button marked 30mA differential test device. The spa stops
operating.
Reset the differential device. The spa re-starts in initiation mode.
Never use your spa if the differential system is faulty.
11