4.15
Information regarding UL
REMARQUE
Le chapitre suivant est toujours en anglais, indépendamment de la langue de la pré-
sente documentation et ce en raison des prescriptions UL.
4.15.1
Field Wiring Power Terminals
•
•
•
MDP90A-...-
0100 (size 1)
X1
0100 (size 1A)
X1
0250
X1
0500
X1
0750
X1
1100
X1
MDA90A-...-
0020 – 0120
X2
0160 – 0240
X2
0320 – 0480
X2
0640 – 1800
X2
MDD90A-...-
0020 – 0040
X2
0020 – 0080
X2
X4
MDP90A-1100
X4B
MDA90A-1400 – 1800
X4
4.15.2
Short Circuit Current Rating
Suitable for use on a circuit capable of delivering not more than
•
Max. voltage is limited to 500 V.
Use 75 °C solid or stranded copper wire only sized at 14 AWG minimum. Suitable
for 1 wire per terminal.
For double axis modules use wire size 12 – 14 AWG.
Tighten terminals to in-lbs (Nm) as follows
Line connection
4.4 – 5.3 (0.5 – 0.6)
4.4 – 5.3 (0.5 – 0.6)
26.6 – 35.4 (3.0 – 4.0)
159.3 – 194.7 (18.0 – 22.0)
159.3 – 194.7 (18.0 – 22.0)
159.3 – 194.7 (18.0 – 22.0)
Motor connection
4.4 – 5.3 (0.5 – 0.6)
13.3 – 15.0 (1.5 – 1.7)
26.6 – 35.4 (3.0 – 4.0)
159.3 – 194.7 (18.0 – 22.0)
Motor connection
4.4 – 5.3 (0.5 – 0.6)
13.3 – 15.0 (1.5 – 1.7)
DC link connection
26.6 – 35.4 (3.0 – 4.0)
DC link connection
97.4 – 106.2 (11.0 – 12.0)
97.4 – 106.2 (11.0 – 12.0)
5000/10000/65000 rms symmetrical amperes when protected by fuses and circuit
breakers as described in the tables below.
Tightening torque in-lbs (Nm)
Power supply module
Braking resistor terminals
X3
X3
X3
X3
X3
X3
Single-axis module
-
-
-
X3
Double-axis module
-
-
All modules (exception below)
-
-
Notice d'exploitation – MOVIDRIVE
Installation
Information regarding UL
4.4 – 5.3 (0.5 – 0.6)
4.4 – 5.3 (0.5 – 0.6)
26.6 – 35.4 (3.0 – 4.0)
26.6 – 35.4 (3.0 – 4.0)
26.6 – 35.4 (3.0 – 4.0)
97.4 – 106.2 (11.0 – 12.0)
-
-
-
-
159.3 – 194.7 (18.0 – 22.0)
-
-
-
PE connection
26.6 – 35.4 (3.0 – 4.0)
-
-
®
modular