2.2 Technical Data

2.2.1 Supply
230VAC (between 208V and 240V) - Frequency: 50/60Hz
Grounding: ! Compulsory!
2.2.2 Fans Electrical Protection
The fans motors provided with the three kits are self-protected against overloading. It is thus NOT
necessary to install an electrical overload protection device. We advise using a short circuit protection
device with the following specifications:
- Starting peak of 150 A for 2 to 4 milliseconds. The "soft stop" function has to be used to avoid this
peak.
- We recommend a class AM or a D type "slow" reaction curves protection device.
Recommended protection calibre/motor type
Type
TAC 170 W
TAC 1/3
TAC 1/2
TAC 3/4
TAC 1/1
2.2.3 Kits Insulation Class
Thermal: B
Mechanical: IP44 - the connectors must be oriented downwards AND mount pass cables (PG) M16 or
M20 on the plastic box where you have previously punched out the holes to allow cable passage. Be
cautious to punch holes properly to keep tightness.
2.2.4 Ambiant Température
-10°C / +55°C
2.2.5 Conformities
CE – UL approved.
calibre
4A
4A
4A
8A
10A
10