1 FUNCTIONALITIES OF THE REGULATION
TAC5 F controller provides the following features:
-
Driving 1 or 2 fans with chosen working mode: constant airflow (CA), constant torque (TQ),
constant measured pressure (CPs), constant calculated pressure (CPf) or constant airflow
linked to 0-10V signal (LS) (i.e. CO2 sensor).
-
Management of 4 timeslots.
-
Alarms on defects, set points, overpressure.
-
Fire alarm airflow/torque management.
-
BOOST function, allowing forcing a pre-set airflow/torque (for fan 1 and 2), overriding the
assigned airflow/torque
-
LCD display on the controller of the settings and working fans.
-
Advanced setup.
The following options can be combined with TAC5 F controller:
-
SAT3 option :
Circuit with 2 relays (O.R.1 and O.R.2) :
Information about "Pressure alarm" (can be configured on O.R.1 or O.R.2)
●
Information about the "FAN ON" (can be configured on O.R.1 or O.R.2)
●
the control of damper(s) "CTin" (can be configured on O.R.1 or O.R.2)
●
-
SAT TAC5 MODBUS option :
Enables the following options:
•
RC TAC5 – simple remote control with a LCD display (2x8 digits).
•
MODBUS RTU communication – configuration and visualization via a centralized
technical management system.
-
SAT ETHERNET option:
•
Remote control with specific App for tablet and smartphone (with a Wi-Fi router or
bridge to Ethernet).
•
Enables MODBUS TCP/IP protocol on Ethernet over twisted pair 10 BASE T network.
-
SAT WIFI option:
•
Remote control with specific App for tablet and smartphone.
•
Enables MODBUS TCP/IP protocol on wireless WIFI network
-
SAT TAC5 KNX Option: KNX Communication
See separate installation manual for each of these options.
5