3.1.3.3.2.4
Wiring to several circuits in parallel with, for each circuits, 2 fans whose
torques are independent
3.1.4
Mode OFF
In TAC5 F master configuration (see § 4.1.2), this mode allows to stop the fans. To restart the fans it's
required to choose one of the other working modes.
3.2 Time slots schedule
The TAC5 F regulation allows to configure 4 time slots (TS) and to set OFF days (fans will be stopped
from 00:00 to 23:59).
For each time slot select:
- In CA mode: the airflow of fans 1 and 2.
- In TQ mode: the percentage of the maximum torque of fans 1 and 2.
- In LS mode: the link LS (percentage of the nominal link).
- In mode CPs or CPf : the pressure setpoint (percentage of the nominal setpoint)
And for each day of the week select: AUTO / OFF (operate as a normal day or as an OFF day).
3.2.1 Setup
The following functions can be configured:
...
...
...
1
CONFIG
Select Y to configure time and date.
TIME? N
If CONFIG TIME is set to Yes
2
SET TIME:
Enter the hour.
xx:xx
3
SET DATE:
Enter the date (day/month/year).
xx/xx/xx
4
TIME
Select Y to activate the time segment scheduling function.
SEGMENT ?N
K1 closed  soft start
K1 open  soft stop
K2  0-10V signal for fan 1, maximum
impedance allowed: 1500 Ω
K3  0-10V signal for fan 2, maximum
impedance allowed: 1500 Ω
Caution: use gold-plated contacts only.