3.1.3.2.2.2
Wiring to 1 circuit with 2 fans whose torques are independent
3.1.3.2.2.3
Wiring to several circuits in parallel with, for each circuits, 1 fan or 2
fans whose torques are dependant
K1 closed soft start
K1 open soft stop
K2 0-10V signal for fan 1, maximum
impedance allowed: 1500 Ω
K3 0-10V signal for fan 2, maximum
impedance allowed: 1500 Ω
Caution: use gold-plated contacts only.
K1 closed soft start
K1 open soft stop
K2 0-10V signal, maximum impedance
allowed: 1500 Ω
K1+K3 closed % on K3 activated
K3 open % on K3 inactive
Caution: use gold-plated contacts only.
30