In LS mode, menu items below are shown if TIME SEGMENT is set to Yes.
For the reference to the base configured link between, see:
in airflow modulation, cfr m³/h≡Vmin and m³/h≡Vmax in the setup,
-
in torque modulation, cfr %TQ≡Vmin and %TQ≡Vmax in the setup.
-
5
TIME 1:
Enter Time Slot 1 starting time. If empty time slot is inactive.
--:--
If 1 fan
6
SET VAL.
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
If 2 dependent Fans
7
SET VAL.
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
8
For Time Slot 1, select airflow/torque ratio between fan 2 and 1.
%F2/F1
100 %
If 2 independent Fans
9
LS on
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 1.
F1 000%
Select 000 to stop the fan, 100% to have the nominal set point.
10
LS on
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 2.
F2 000%
Select 000 to stop the fan, 100% to have the nominal set point.
11
TIME 2:
Enter Time Slot 2 starting time. If empty time slot is inactive.
--:--
If 1 fan
12
SET VAL.
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
If 2 dependent Fans
13
SET VAL.
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
14
For Time Slot 2, select airflow/torque ratio between fan 2 and 1.
%F2/F1
100 %
If 2 independent Fans
15
LS on
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 1.
F1 000%
Select 000 to stop the fan, 100% to have the nominal set point.
16
LS on
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 2.
F2 000%
Select 000 to stop the fan, 100% to have the nominal set point.
17
TIME 3:
Enter Time Slot 3 starting time. If empty time slot is inactive.
--:--
If 1 fan
18
SET VAL.
For Time Slot 3, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
If 2 dependent Fans
19
SET VAL.
For Time Slot 3, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
20
For Time Slot 3, select airflow/torque ratio between fan 2 and 1.
%F2/F1
100 %
36