Swegon TAC5F Manuel D'installation page 34

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

In LS mode, menu items below are shown if TIME SEGMENT is set to Yes.
For the reference to the base configured link between, see:
in airflow modulation, cfr m³/h≡Vmin and m³/h≡Vmax in the setup,
-
in torque modulation, cfr %TQ≡Vmin and %TQ≡Vmax in the setup.
-
5
TIME 1:
Enter Time Slot 1 starting time. If empty time slot is inactive.
--:--
If 1 fan
6
SET VAL.
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
If 2 dependent Fans
7
SET VAL.
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
8
For Time Slot 1, select airflow/torque ratio between fan 2 and 1.
%F2/F1
100 %
If 2 independent Fans
9
LS on
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 1.
F1 000%
Select 000 to stop the fan, 100% to have the nominal set point.
10
LS on
For Time Slot 1, enter coefficient (%) applied to the base configured link for fan 2.
F2 000%
Select 000 to stop the fan, 100% to have the nominal set point.
11
TIME 2:
Enter Time Slot 2 starting time. If empty time slot is inactive.
--:--
If 1 fan
12
SET VAL.
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
If 2 dependent Fans
13
SET VAL.
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
14
For Time Slot 2, select airflow/torque ratio between fan 2 and 1.
%F2/F1
100 %
If 2 independent Fans
15
LS on
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 1.
F1 000%
Select 000 to stop the fan, 100% to have the nominal set point.
16
LS on
For Time Slot 2, enter coefficient (%) applied to the base configured link for fan 2.
F2 000%
Select 000 to stop the fan, 100% to have the nominal set point.
17
TIME 3:
Enter Time Slot 3 starting time. If empty time slot is inactive.
--:--
If 1 fan
18
SET VAL.
For Time Slot 3, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
If 2 dependent Fans
19
SET VAL.
For Time Slot 3, enter coefficient (%) applied to the base configured link for fan 1.
Select 000 to stop the fan, 100% to have the nominal set point.
LS 000%
20
For Time Slot 3, select airflow/torque ratio between fan 2 and 1.
%F2/F1
100 %
36