If # FAN=F1 : only 1 fan
10
% sur K3?
11
CONFIG
TIME? N
12
TIME
SEGMENT ?N
13
DAY OFF
N
14
RESET
ALARMS?
15
END SETUP
If #FAN=F1 + F2 : 2 fans
If F2=%F1 is set to yes: 2 dependent fans
10
% sur K3?
11
%F1/F2
12
CONFIG
TIME? N
13
TIME
SEGMENT ?N
14
DAY OFF
N
15
RESET
ALARMS?
16
END SETUP
3.1.3.2.2 Wiring Diagrams
3.1.3.2.2.1
Wiring to 1 circuit with 1 fan or 2 fans whose torques are dependant
Select multiplier of LS link when terminals +12V and K3 are closed ('night' setup).
Select Y to configure time and date. See § 3.2.1
Select Y to activate the time segment scheduling function. See § 3.2.1
Select Y if you wish to activate the day OFF option. See § 3.2.1
Possibility to reset the alarms. Y or N?
The setup is then completed.
Select multiplier of LS link when terminals +12V and K3 are closed ('night' setup).
Choose the rate between fan 2 and 1 airflow
Select Y to configure time and date. See § 3.2.1
Select Y to activate the time segment scheduling function. See § 3.2.1
Select Y if you wish to activate the day OFF option. See § 3.2.1
Possibility to reset the alarms. Y or N?
The setup is then completed.
K1 closed soft start
K1 open soft stop
K2 0-10V signal, maximum impedance
allowed: 1500 Ω
K1+K3 closed % on K3 activated
K3 open % on K3 inactive
Caution: use gold-plated contacts only.
29