3.5.1 Wiring Diagram
3.6 Opening / closing of dampers « CT » (via SAT3 option)
The opening and closing of (a) damper(s) mounted at both supply and exhaust air inlets are
automatically managed by the TAC5 F regulation (SAT3 option, damper(s) and actuator(s) are provided
by the installer).
The actual fan startup is delayed to allow prior opening of dampers. When fans are stopped the
dampers are closed.
3.6.1 Setup
By default, no output for CT is configured. The setup of the CT can be modified using ADVANCED
SETUP to have the CT output either on O.R.1 or on O.R.2 of SAT3 (option).
http://www.swegon.com/
Full details: see the technical documentation on our website
3.6.2 Wiring Diagram
In this diagram, CT has been configured on O.R.2 SAT3 output relay; use O.R.1 if configured on
O.R.1.