If #FAN=F1 + F2 : 2 fans
If F2=%F1 is set to yes: 2 dependent fans
6
%TQ K1?
7
%TQ K2?
8
%TQ K3?
9
%F1/F2
If F2=%F1 is set to no: 2 independent fans
6
%TQ-1 F1?
7
%TQ-2 F1?
8
%TQ-3 F1?
9
%TQ-1 F2?
10
%TQ-2 F2?
11
%TQ-3 F2?
12
CONFIG
TIME? N
13
TIME
SEGMENT ?N
14
DAY OFF
N
15
RESET
ALARMS?
16
END SETUP
3.1.3.1.2 Wiring Diagrams
3.1.3.1.2.1
Wiring 1 circuit to 3 external contacts
Select percentage of maximum torque 1 for fan 1(contacts between terminals K1
and +12V closed)
Select percentage of maximum torque 2 for fan 1 (contacts between terminals K2
and +12V closed)
Select percentage of maximum torque 3 for fan 1 (contacts between terminals K3
and +12V closed)
Choose the rate between fan 2 and 1 airflow
Select percentage of maximum torque 1 for fan 1(contacts between terminals K1
and +12V closed)
Select percentage of maximum torque 2 for fan 1 (contacts between terminals K2
and +12V closed)
Select percentage of maximum torque 3 for fan 1 (contacts between terminals K3
and +12V closed)
Select percentage of maximum torque 1 for fan 2 (contacts between terminals K1
and +12V closed)
Select percentage of maximum torque 2 for fan 2 (contacts between terminals K2
and +12V closed)
Select percentage of maximum torque 3 for fan 2 (contacts between terminals K3
and +12V closed)
Select Y to configure time and date. See § 3.2.1
Select Y to activate the time segment scheduling function. See § 3.2.1
Select Y if you wish to activate the day OFF option. See § 3.2.1
Possibility to reset the alarms. Y or N?
The setup is then completed.
K1 closed  Percentage of max torque %TQ K1
K2 closed  Percentage of max torque %TQ K2
K3 closed  Percentage of max torque %TQ K3
K1/K2/K3 open  soft stop
Caution K1/K2/K3: Use gold-plated contacts only