You have purchased a product made by JUNG
PUMPEN and with it, therefore, also excellent qua-
lity and service. Secure this service by carrying out
the installation works in accordance with the inst-
ructions, so that our product can perform its task
to your complete satisfaction. Please remember
that damage caused by incorrect installation or
handling will adversely affect the guarantee.
Therefore please adhere to the instructions in
this manual!
As with all electrical devices, this product can also
fail to operate due to an interruption in the electri-
city supply or due to a technical defect. If this could
result in damage, a mains-independent alarm sys-
tem must be installed. Depending on the applica-
tion, you may also wish to install an emergency
power generator, or a second system as a back-up.
Safety instructions
This instruction manual contains essential infor-
mation that must be observed during installation,
operation and servicing. It is therefore important
that the installer and the responsible technician/
operator read this instruction manual before the
equipment is installed and put into operation. The
manual must always be available at the location
where the pump or the plant is installed.
Failure to observe the safety instructions can lead
to the loss of all indemnity.
Labelling of instructions
In this instruction manual, safety information is dis-
tinctly labelled with particular symbols. Disregard-
ing this information can be dangerous.
General danger to people
Warning of electrical voltage
ATTENTION! Danger to equipment and operation
Qualification and training of personnel
All personnel involved with the operation, servic-
ing, inspection and installation of the equipment
must be suitably qualified for this work and must
have studied the instruction manual in depth to
ensure that they are sufficiently conversant with its
contents. The supervision, competence and areas
of responsibility of the personnel must be precisely
regulated by the operator. If the personnel do not
have the necessary skills, they must be instructed
and trained accordingly.
Safety-conscious working
The safety instructions in this instruction manual,
the existing national regulations regarding acci-
dent prevention, and any internal working, oper-
ating and safety regulations must be adhered to.
Safety instructions for the operator/user
All legal regulations, local directives and safety
regulations must be adhered to.
The possibility of danger due to electrical energy
must be prevented.
Leakages of dangerous (e.g. explosive, toxic, hot)
substances must be discharged such that no dan-
ger to people or the environment occurs. Legal
regulations must be observed.
Safety instructions for installation, inspection
and maintenance works
As a basic principle, works may only be carried out
to the equipment when it is shut down. Pumps or
plant that convey harmful substances must be de-
contaminated.
All safety and protection components must be re-
fitted and/or made operational immediately after
the works have been completed. Their effective-
ness must be checked before restarting, taking
into account the current regulations and stipula-
tions.
Unauthorised modifications, manufacture of
spare parts
The equipment may only be modified or altered
in agreement with the manufacturer. The use of
original spare parts and accessories approved by
the manufacturer is important for safety reasons.
The use of other parts can result in liability for con-
sequential damage being rescinded.
Unauthorised operating methods
The operational safety of the supplied equipment
is only guaranteed if the equipment is used for its
intended purpose. The limiting values given in the
"Technical Data" section may not be exceeded un-
der any circumstances.
Instructions regarding accident prevention
Before commencing servicing or maintenance
works, cordon off the working area and check that
the lifting gear is in perfect condition.
Never work alone. Always wear a hard hat, safety
glasses and safety shoes and, if necessary, a suit-
able safety belt.
Before carrying out welding works or using electri-
cal devices, check to ensure there is no danger of
explosion.
People working in wastewater systems must be
vaccinated against the pathogens that may be
found there. For the sake of your health, be sure to
pay meticulous attention to cleanliness wherever
you are working.
Make sure that there are no toxic gases in the
working area.
Observe the health and safety at work regulations
and make sure that a first-aid kit is to hand.
In some cases, the pump and the pumping me-
dium may be hot and could cause burns.
For installations in areas subject to explosion haz-
ards, special regulations apply!
English
Technical data
Operating voltage
• 1/N/PE x 230 V, 50 Hz (AD/BD 00 E)
• 3/N/PE x 230/400 V, 50 Hz
Power consumption
• AD max. 2 W (Standby <1W)
• BD max. 4 W (Standby <1W)
Switching capacity
• AD 00E 1 x 2.2 kW AC3, 230 V
• BD 00E 2 x 2.2 kW AC3, 230 V
• AD... 1 x 4 kW AC3, 400V
• BD... 2 x 4 kW AC3 at 400 V
Control voltage 230 VAC / 12 VDC
Ambient temperature
• -20° Celsius to 50° Celsius
Humidity Up to 90rH with no condensation
Terminals up to 2.5 mm²
Housing dimensions
• AD... H 250 x B 250 x T 155
• BD... H 430 x W 250 x D 155
Housing protection class IP 44
Weight AD approx. 2 kg, BD approx. 6 kg
Motor protection
• AD 00: ohne
• BD 00: 6 A, BD 00E: 10 A
• AD 25: 2,5-4,0 A
• AD 46: 4,0-6,0 A
• AD 610: 6,3-9,0 A
• BD 25: 2,5-4,0 A
• BD 46: 4,0-6,3 A
• BD 610: 6,3-10 A
Pre-fuse
• AD: 16 A
• BD 00 E: 20 A
• BD 00: 16 A
• BD 25: 16 A
• BD 46: 20 A
• BD 610: 25 A
Description
Electronic control unit for level control of one (AD)
or two (BD) d.o.l. starting submersible pump(s).
Up to three (AD) or four (BD) level contact sensors
can be connected.
For duplex pump units the power-up sequence of
pump 1 and pump 2 alternates automatically af-
ter every base-load pumping process. The resting
pump is switched on in the event of high water or
a pump fault.
Duplex units can be operated optionally without
peak-load function (i.e. no parallel pump operati-
on). Automatic switch-over to the standby pump
will occur in the event of failure.
The control unit incorporates mains-dependent
LED failure indicators and an alarm buzzer to in-
dicate faults. One (AD) or two (BD) potential-free
centralised alarm contacts can be used as additi-
onal remote failure indicators. An optional 9V re-
chargeable battery can also be fitted to sustain an
alarm facility even if a power cut occurs. The bat-
tery pack can supply the alarm system with power
for about one hour of continuous use.
5