High Voltage Wiring Connections

Contact with hazardous voltage could result in death or serious injury.
Disconnect and lock out all power before installing or servicing equipment.
Connect the motor, the drive, metal plumbing, and all other metal near the motor or cable to the
power supply ground terminal using wire no smaller than motor cable wires.
Install and wire in accordance with all applicable local and national electrical construction codes.

Ground Connections

Risk of damage to drive
Ensure that the system is properly grounded all the way to the service entrance panel. Improper
grounding may result in loss of voltage surge protection.
Nonmetallic enclosure does not provide grounding between conduit connections. When using
metal conduit, install Listed grounding bushings and Listed No. 10 AWG minimum wires per national
and local codes.
When installing rigid metal conduit, connect conduit to hub BEFORE hub is connected to drive
enclosure.
Follow these grounding requirements to ensure safety and performance.
1.
Make sure a service entrance ground rod is properly installed and connected.
2. Service Entrance Panel.
3. An input power ground wire from the supply panel must be connected to the drive.
4. A dedicated output ground wire from the drive must be connected to the motor. Motor and ground
wires must be bundled together.
,
or malfunction can occur.
ELECTRICAL INSTALLATION
High Voltage Wiring Connections
19