11.5.1 MANAGEMENT ALARMS

To select the submenu Alarm management coming out of the parameters of the SET menu system, follow these steps:
-
press SB6 to return to the HOME PAGE of the configuration menu .
-
Press SB10 to select Alarm Management.
ENGLISH
Submenu SET I/O parameter
Description
3.1 Input DIG. RCTerminals: 15 - 16
Configuration of closing of digital input DIG0.
0) No change: OFF.
1) Enables remote control: RC.
2) External Fault
3) H2O leak
4) Change P.Set VAL2.
3.2 D.O. 1
Configuration of change of RL1.
0: No
1: Fault
2: Automatic
3: Manual
4: Asset value within the proportional band value
of Setpoint
5: Pump running
6: Lack Water
7: External fault
3.3 D.O. 2
Configuration of change of RL2.
0: No
1: Fault
2: Automatic
3: Manual
4: Asset value within the proportional band value
of Setpoint
5: Pump running
6: Lack Water
7: External fault
3.4 AN. OUT 1
Configuration of analog output 1.
0-Output: OFF.
1-Inverter frequency proportional output: Hz.
2-Inverter current proportional output: A
3.6 System supervisor
OFF – no supervision;
GSM - supervision by the additional gsm
Module.
3.7
GSM test message
Allows to choose any number of days to
receive a test message.
56
Field
Default
0 - 4
0: OFF
0 - 7
1: Fault
0 - 7
0: OFF
0 - 2
0: OFF
0 - 1
0:OFF
0 - 4
2: Every 14 days