11.6 GSM MODULE CONFIGURATION
- Carry out installation and the first start-up procedure as indicated in the manual of the GSM module, referring to
the drawing below for references concerning this panel.
- After installation and the first start-up, check that there is no indication of the alarm AL5.
- Check the sending of an alarm SMS by causing an alarm situation, for example temporarily disconnecting the
jumper or the minimum pressure switch between terminals 15-16 (or 7-8 depending on the settings).
In the event of an alarm the GSM module will send a message containing the description of the active alarms.
- pump maintenance;
- parameters error;
- faulty sensor;
- motors thermal protection;
- inverter alarm;
- no comunication with inverter;
- overpressure;
- lack of water;
- external fault;
- minimum pressure.