7
TYPES OF OPERATION
The electric panel, through the control panel, can be set to operate for different types of plant:
7.1 Pressurized water plant set booster
Power protection and control with inverter of the first electric pump that start.
Automatic start of the second and/or third electric pump power supply by the net.
Automatic exchange of the inverter when restarted.
Automatic starting of the electrical pump stopped in the case that the inverter is lock.
Automatic starting of the electrical pump stopped in the case that the inverter is lock with signalization on the
display and remote control.
Adjusting at relative or differential pressure constant with the opportunity to select the value of P. Set in control
panel or by remote control.
Two relay outputs configurable as:
- Plant running
- Alarm
- P. Set reached.
Remote control configurable as:
- Start / stop plant.
- external fault with signalation alarm as 256.
- Lack water with signalation alarm as H2O .
- Change P.Set in Val2.
Analog output 0 -: - 10V configurable as:
- Speed motors.
- Total current motors
-- Managing and storing historical alarms and hours worked reached.
7.2 Heating plants (circulator) with differential constant pressure or with differential constant temperature.
Power protection and control of the electric pumps.
Automatic exchange of the order of departure between electric pumps every 24 hours or with time set.
Automatic starting of the electrical pump stopped in the case that the inverter is lock with signalization on the
display and remote control.
Regulation at constant differential pressure with possibility of selecting the value of P. Set in the control panel or
by remote control.
Configurable relay outputs and controls with the same functions as described in chap. 7.1.
7.3 Osmosis systems at constant flow.
Power protection and control of the electric pumps.
Automatic exchange of the order of departure between electric pumps every 24 hours or with time set.
Automatic starting of the electrical pump stopped in the case that the inverter is lock with signalization on the
display and remote control.
Regulation at constant differential pressure with possibility of selecting the value of P. Set in the control panel or
by remote control.
-- Configurable relay outputs and controls with the same functions as described in chap. 7.1.
ENGLISH