Table Of Alarms Displayed On The Kl1 Control Unit; Minimum Pressure; Table Of Parameters Dedicated To Serivice Ebara To Be Established In The Kl1 Control Unit - EBARA 2SP EFC 1,5T-1 Instructions Pour L'installation Et La Maintenance

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

8.2.4 TABLE OF ALARMS DISPLAYED ON THE KL1 CONTROL UNIT

ALARM LIST
1=
MOTOR MAINTENANCE
PARAMETER ERROR
2=
TRANSDUCER
4=
8=
MOTOR OVERLOAD
16=
INVERTER
32=
OVERPRESSURE
H2O?

MINIMUM PRESSURE

(THREE AUTOMATIC RESETS)
MINIMUM PRESSURE
64=
(MANUAL RESET)
WARNING: Multiple alarms are displayed one at a time.
WARNING: - The triggering of alarm n. 4 (faulty sensor) and/or the control unit failure alarm determine the automatic
starting of the system with pressure switches (check the efficiency of the expansion tanks).
- The triggering of alarm n. 16 (inverter failure) disconnects the pump powered by the inverter and maintains
pressure regulation by the Systemcontroller.
The message "MOTOR MAINTENANCE alarm 1" is cancelled by moving the cursor to
table 8.2.3, the motor that is scheduled for maintenance, then selecting ON using the
8.2.5 TABLE OF PARAMETERS DEDICATED TO SERIVICE EBARA TO BE ESTABLISHED IN THE KL1
CONTROL UNIT
Parameter
Enter key
0
Language
Languages in which the parameters are written
1: ENGLISH
(Italian, English, French, German, Spanish).
Italian, English, French, German, Spanish*.
0
The boldface parameters must be calibrated during the system startup phase.
* = Spanish language is not in the control unit (supplied on request).
ENGLISH
DESCRIPTION
It appears when the hours established in the P maint. parameter have been exceeded.
It appears when the set Pressure is higher than the transducer's full scale or pres. Is higher
than the Pressure transmitter or Pres. Nom. Is higher than Pressure transmitter
It appears when there is no signal from the transducer
It appears when the motor overload protections are triggered.
It appears when the inverter shuts down.
It appears when the safe pressure is exceeded.
It appears when the pressure drops to minimum; software control from the control unit
with three automatic attempts to reset the protection and shut-down at the fourth attempt,
with manual reset. The protection triggering time is one minute. The first three times that
the protection is triggered, the message "H2O?" appears on the display, the fourth time
the message "64" appears.
Triggering of minimum pressure switch or float switch, connected to terminals 11 – 12.
Description
Enter the SERVICE EBARA key
1
2
3
4
Range
0-:-99999
0 -:- 4
24
and selecting, at the bottom of
DECREASE
key and striking the
ENTER
SHIFT
Meas.
SetUP
unit
Service
/
20009
/
English
key.

Publicité

Table des Matières
loading

Table des Matières