4.
RESPONSIBILITY
The Manufacturer does not vouch for correctoperation of the panels or for any damage that they may
cause if they have been tampered with, modified and/or run outside the recommended work range or in
contrast with other indications given in this manual.
5.
INSTALLATION
Strict observance of the power supply values shown in the electrical rating plate is required .
The electrical panel must be installed on a dry surface, in an atmosphere that is free from oxidizing or corrosive
gases, and where no vibrations occur. If installed outdoors, the units must be fully protected from direct
sunlight. Suitable measures must be taken to ensure that the ambient temperature is kept within the operating
limits specified below. Moreover, the installation personnel must make sure that the cable glands are perfectly
sealed.
We recommend installing an earth leakage circuit breaker to protect the plant that is correctly sized,
type A, with the leakage current controlled of 100 mA and more,selective, protected against untimely shots.The
differential switch will automatically be marked by one of two symbols:
To the connection at the electrical panel provide a three-pole switch with opening contact distance of 3 mm and fuses
type gG (rapid) with current value appropriate to the group pumps to powered.
IT IS RECOMMENDED THE PROPER AND SAFE GROUND CONNECTION INSTALLATION!
MOTOR CABLE LENGTHS:
- L ≤ 10m:
NOT NEED ANY FERRITE
- 10m < L ≤ 50m:
WRAP 5 COILS OF THE THREE MOTOR CABLE (EXCLUDING GROUND) IN FERRITE SUPPRESSION XLM1
- L > 50m:
USE THE MOTOR REACTANCE XLL1
ENGLISH
35