3.2.1

Setting the opening direction

The opening direction is adjusted by means of DIL switch 6.
DIL 6 ON
A
3.2.2
Setting the function of the drive unit
The switches DIL 1, 2 and 3 determine the function of the drive unit. Fig. 39
DILswitch
1
2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
3.2.3

Setting the speed

DIL switches 4 and 5 determine the opening speed (Vo) and the closing speed (Vc).
Warning:
For safety reasons, the maximum door weights specified in chart 3 for each speed setting
must not be exceeded.
0602-999-11c_2008.09.p65
3
OFF
Open-Close in dead man's mode (AZ without SH)
OFF
Open-Close on pulse in opening direction (AZ with SH OPEN)
OFF
Open-Close on pulse in closing direction (AZ with SH CLOSE)
OFF
Open-Close on pulse in both directions (AZ with SH OPEN/CLOSE)
ON
Step-by-step control Open-Close (SS AZ)
ON
Step-by-step control Open-Stop-Close (SS AHZ)
ON
Unassigned
ON
Fully automatic (VA)
0602-999/11c
A
View A
Drive unit function
ASL-S
26-40
DIL 6 OFF
factory setting
Tab. 2
Fig. 38