SAMPLES OF ALLOWABLE PLENUM/DUCTING ARRANGEMENTS:
ALLOWABLE
"ADD ON"
WOOD
FURNACE
"ADD ON"
WOOD
FURNACE
6.6

EMBER STOP

For installations on combustible fl ooring an ember stop protective fl oor covering must be installed.
An ember stop of minimum 0.015" thick sheet metal extending from 18" off the front of the fi rebox door
right through protruding out the back of the furnace and with a width which extends 9" each side of the
fi rebox door is required.
Carpet or other fl oor covering shall be removed before placement of ember stop sheet.
Refer to Section 7.1 of CAN/CSA-B365-01 for complete details of fl oor protection.