The Napoleon HMF150 may take outside combustion air directly into the appliance through a 4" inlet collar at
the back of the unit. This inlet is to supply combustion air for the HMF150 Wood Furnace only.
Secure and seal the intake liners to the collars using 3 sheet metal screws, and high temperature sealant.
Insulating the intake liners is recommended in colder climates to prevent condensation from occurring.
The 4" inlet can also draw combustion air from the room provided adequate make up air is available.
Fresh air makeup for the oil furnaces must follow criteria set in installation standard CSA B139-09 "Installation
Code For Oil Burning Equipment", and installed by a certifi ed oil mechanic.
Fresh air makeup for gas fi red furnaces must follow criteria set in installation standard CAN/CGA-B149.1 or
CAN/CGA-B149.2.
Fresh air makeup solid fuel furnaces must follow criteria set in installation standard CAN/CSA-B365.
WHEN INSTALLING A SYSTEM FOR MAKE UP FRESH AIR, THE INSTALLER MUST TAKE INTO
ACCOUNT A SATISFACTORY AIR MAKE UP RATE IN THE LIKELIHOOD THAT MORE THAN ONE
FUEL-BURNING FURNACE IN A MULTI FURNACE CONFIGURATION MAY OPERATE AT THE SAME
TIME.