Remote Controller Installation; Optional Installation Work; Optional Kit Installation - Fujitsu 9384203007-04 Manuel D'installation

Climatiseur unite interieure ( type a conduit)
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

(1) Remove the control box cover and install each connection wire.
Attach the conduit connector on the wiring connecting port.
(The grommet edging and the connection cable clamp are not used.)
■ Connection cable
Control line
Power line
■ Remote controller cable
Red
Remote controller
*Earth (Ground) the remote controller if it has a earth (ground) wire.
(2) After wiring is complete, secure the remote controller cable and connection cable
with the wire clamper or cable tie.
Remote controller cable
(3) Seal the cable outlet or other gaps with putty to prevent dew condensation or insect
from entering the electric control box.
(4) Replace the control box cover.
En-12
9384203007-04.indb 12
9384203007-04.indb 12
Lock nut
(Locally purchased)
Conduit connector
(Locally purchased)
Conduit
connector
Outdoor
unit
Earth
(ground)
White
Remote
controller
cable
Connection cable
(to outdoor unit)
CAUTION
• Do not bundle the remote controller cable, or wire the remote controller cable in par-
allel, with the indoor unit connection wire (to the outdoor unit) and the power supply
cable. It may cause erroneous operation.
• Tighten the indoor unit connection wire and power supply indoor and outdoor unit,
terminal board connections fi rmly with the terminal board screws. Faulty connection
may cause a fi re.
• Connect the indoor unit connection wire by matching the numbers of the outdoor and
indoor units terminal board numbers as shown in terminal label.
• Be sure to refer to the connection diagram for the correct fi eld wiring. Wrong wiring
causes malfunction of the unit.
(5) Fix the conduit with the supporters as shown below.
Conduit (Power supply cable)
Indoor unit
30 in
54 in
(756 mm)
(1,361 mm)
or less
or less

3. 8. Remote controller installation

To install and set the remote controller, refer to the installation manual of the remote
controller (wired type).

4. OPTIONAL INSTALLATION WORK

4. 1. Optional kit installation

WARNING
Regulation of cable diff ers from each locality, refer in accordance with local rules.
Terminal
(External in)
External out
Remote sensor
This air conditioner can be connected with the following optional kits.
For details on how to install optional parts, refer to the installation manual included in each
item.
Connector No.
CN48
IR receiver unit (UTY-LBTUM)
CN5
Remote sensor (UTY-XSZX)
CN47*1
External connect kit (UTY-XWZXZG)
External input and output PCB (UTY-XCSX)
CN65*2
Wire kit (UTY-XWZXZJ)
CN67
*1: For external output terminal setting, refer to Function No.60 in "7. FUNCTION SETTING".
*2: Other options (WLAN adapter, converters, etc.) may be available by using the optional
External input and output PCB.
When external input and output PCB is used, connect it with wire kit.
*3: For using optional parts, refer to the optional parts manual. In addition, prepare the
separate power source unlike the manual contents.
Supporter
54 in
54 in
(1,361 mm)
(1,361 mm)
or less
or less
External in/out PCB (Connect with Wire kit)
Option type
External Heater*
3
2020/12/04 12:44:47
2020/12/04 12:44:47