Multiple Remote Control; Field Setting; Dip Switch 101 Setting; Function Setting - Fujitsu 9384203007-04 Manuel D'installation

Climatiseur unite interieure ( type a conduit)
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

A, B, C, D, E : Remote controller cable. (Refer to "2. 5. Electrical requirement")
A+B+C+D+E ≤ 1640 ft (500 m)
Indoor unit 1
Indoor unit 2
Remote controller
cable
Remote controller

5. 2. Multiple remote control

Up to 2 remote controllers can be used to operate one indoor unit
I.U.
A
Primary
A, B : Remote controller cable. (Refer to "2. 5. Electrical requirement")
A ≤ 1640 ft (500 m), A+B ≤ 1640 ft (500 m)

6. FIELD SETTING

6. 1. DIP switch 101 setting

■ Fan delay setting
This setting can be used when the auxiliary heater is mounted.
When the operation is stopped when the indoor unit is operating with an auxiliary heater,
the operation continues 1 minutes.
Change the following settings by using the DIP switch.
DIP SW state
DIP switch 101
ON
1
-
2
-
3
Enable ♦
WARNING!
WHEN ELECTRIC AUXILLARY HEAT IS ADDED,
INSTALLER MUST VERIFY DIP SWITCH SW101-3 IS IN
THE ON POSITION!
En-14
9384203007-04.indb 14
9384203007-04.indb 14
Indoor unit 3
Indoor unit 4
Remote controller
cable
I.U.
A
B
Primary Secondary
(♦... Factory setting)
Details
OFF
-
Cannot be used (Do not Change)
-
Cannot be used (Do not Change)
Disable
Fan delay setting

7. FUNCTION SETTING

To change the function settings, refer to the procedures described in the installation
manual of the remote controller (wired type).
The function settings are as follows.

7. 1. Function details

■ Filter sign
Select appropriate intervals for displaying the fi lter sign on the indoor unit according to the
estimated amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
Function
Setting
Number
Value
00
01
Long interval (4400 hours)
11
02
Short interval (1250 hours)
03
■ Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature correction values show the diff erence from the Standard setting "00"
(manufacturer's recommended value).
Setting
Function Number
Value
00
01
02
03
04
05
06
07
08
30
31
(For cooling)
(For heating)
09
10
11
12
13
14
15
16
17
■ Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both "01".
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Setting
Function number
value
00
01
02
03
04
05
06
07
08
35
36
(For cooling)
(For heating)
09
10
11
12
13
14
15
16
17
(♦... Factory setting)
Setting Description
Standard (2500 hours)
No indication
(♦... Factory setting)
Setting Description
Standard setting
No correction 0 °F (0.0 °C)
-1 °F (-0.5 °C)
-2 °F (-1.0 °C)
-3 °F (-1.5 °C)
More
-4 °F (-2.0 °C)
Cooling
Less
-5 °F (-2.5 °C)
Heating
-6 °F (-3.0 °C)
-7 °F (-3.5 °C)
-8 °F (-4.0 °C)
+1 °F (+0.5 °C)
+2 °F (+1.0 °C)
+3 °F (+1.5 °C)
Less
+4 °F (+2.0 °C)
Cooling
More
+5 °F (+2.5 °C)
Heating
+6 °F (+3.0 °C)
+7 °F (+3.5 °C)
+8 °F (+4.0 °C)
(♦... Factory setting)
Setting description
No correction
No correction 0 °F (0.0 °C)
-1 °F (-0.5 °C)
-2 °F (-1.0 °C)
-3 °F (-1.5 °C)
More
-4 °F (-2.0 °C)
Cooling
Less
-5 °F (-2.5 °C)
Heating
-6 °F (-3.0 °C)
-7 °F (-3.5 °C)
-8 °F (-4.0 °C)
+1 °F (+0.5 °C)
+2 °F (+1.0 °C)
+3 °F (+1.5 °C)
Less
+4 °F (+2.0 °C)
Cooling
More
+5 °F (+2.5 °C)
Heating
+6 °F (+3.0 °C)
+7 °F (+3.5 °C)
+8 °F (+4.0 °C)
2020/12/04 12:44:48