■ Auto restart
Enable or disable automatic restart after a power interruption.
Function
Setting
Number
Value
00
40
01
* Auto restart is an emergency function such as for power outage etc. Do not attempt to
use this function in normal operation. Be sure to operate the unit by remote controller or
external device.
■ Room temperature sensor switching
(Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both"
(01).
Function
Setting
Number
Value
00
42
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
* Remote controller sensor must be turned on by using the remote controller
■ Cold air prevention
*This setting is to disable the cold air prevention function during heating operation. When
disabled, the fan setting will always follow the setting on the remote controller. (Excluding
defrost mode).
Function
Setting
Number
Value
00
43
01
■ External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function
Setting
Number
Value
00
01
46
02
03
■ Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to
"Wired remote controller" (01). This function will only work if the function setting 42 is set
at "Both" (01)
Function
Setting
Number
Value
00
48
01
■ Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation
when the outdoor unit is stopped during cooling operation.
Function
Setting
Number
Value
00
49
01
02
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting.
*When using a wired remote controller without Indoor unit fan control for energy saving for
cooling function, or when connecting a single split converter, the setting cannot be made
by using the remote controller. Set to "00" or "01".
To confi rm if the remote controller has this function, refer to the operating manual of each
remote controller.
9384203007-04.indb 15
9384203007-04.indb 15
(♦... Factory setting)
Setting Description
Enable
♦
Disable
(♦... Factory setting)
Setting Description
Indoor unit
♦
Both
(♦... Factory setting)
Setting Description
Enable
♦
Disable
(♦... Factory setting)
Setting Description
♦
Operation/Stop mode 1
(Setting prohibited)
Forced stop mode
Operation/Stop mode 2
(♦... Factory setting)
Setting Description
Both
Wired remote controller
♦
(♦... Factory setting)
Setting description
Disable
Enable
Remote controller
♦
■ Switching functions for external output terminal
Functions of the external output terminal can be switched.
Setting
Function Number
Value
00
01-04
Cooling thermostat status
05
06
60
07-08
Cooling thermostat status
09
10
11
Refer to the Design & technical manual.
■ Control switching of external heaters
Sets the control method for the external heater being used.
For details of the control method, see the Design & Technical Manual.
Setting
Function Number
Value
00
01
02
Heat pump prohibition control
Heater selection control using
03
Heater selection control using
04
61
05
Auxiliary heater control by outdoor temperature 3
06
07
08
09
■ Operating temperature switching of external heaters
• Sets the temperature conditions when the external heater is ON.
• For the temperature conditions, see "Temperature conditions when the external heater is
ON". For a more detailed explanation, see the Design & Technical Manual.
Setting
Function Number
Value
00
01
02
03
04
05
06
07
08
62
09
10
11
12
13
14
15
16
17
(♦... Factory setting)
Setting Description
Operation status
♦
Heating operation status
Operation status
Error status
Fresh air control
Auxiliary heater
(♦... Factory setting)
Setting Description
Auxiliary heater control 1
♦
Auxiliary heater control 2
outdoor temperature 1
outdoor temperature 2
Auxiliary heat pump control
Auxiliary heat pump control
by outdoor temperature 1
Auxiliary heat pump control
by outdoor temperature 2
Auxiliary heat pump control
by outdoor temperature 3
(♦... Factory setting)
Setting Description
Setting 0
♦
Setting 1
Setting 2
Setting 3
Setting 4
Setting 5
Setting 6
Setting 7
Setting 8
Setting 9
Setting 10
Setting 11
Setting 12
Setting 13
Setting 14
Setting 15
Setting 16
Setting 17
En-15