00
Auto restart
40
01
00
Cool Air
43
Prevention
01
00
Emergency
External
01
46
control
02
Forced stop
00
Display only
Error report
47
target
01
Fan set-
00
ting when
cooling
49
thermostat
OFF
01
8. TEST RUN
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using Remote Controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
fl ash slowly at the same time.
For details, please refer to the Manual of "IR Receiver Unit" or "Wired Remote Controller".
9. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS
Has the indoor unit been installed
correctly?
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been
completed?
Does water drain easily from the indoor
units?
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)?
Is the connection cable the specified
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner
operation by remote controller
or external device?
After installation is completed, has the
proper operation and handling been
explained to the user?
9373385141-01_IM.indb Sec1:16
9373385141-01_IM.indb Sec1:16
Enable or disable automatic
Enable
system restart after a power
○
outage.
Disable
○
Super low
Restrain the cold airfl ow
with making the airfl ow
Follow the
lower when starting heating
setting on
operation. To correspond to
the remote
the ventilation, set to 01.
controller
○
Start/Stop
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant
stop
systems will be disabled.
* If forced stop is set, indoor
unit stops by the input to
the external input terminals,
and Start/Stop by a remote
controller is restricted.
○
All
Change the target for report-
ing errors. Errors can either
on central
be reported in all locations, or
remote
only on the wired remote.
controller
Follow the
When set to 01, the fan stops
setting on
when the thermostat is OFF
○
the remote
in cooling operation. Con-
controller
nection of the wired remote
controller (2-wire type or
3-wire type) and switching its
Stop
thermistor are necessary.
CHECK
If not performed correctly
Vibration, noise,
indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn
damage
No operation, heat or burn
damage
Short circuit
No operation, heat or burn
damage
No cooling, No heating
No operation
10. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote control-
ler display. If you use a wireless remote controller, the lamp on the photodetector unit
will output error codes by way of blinking patterns. See the lamp blinking patterns and
error codes in the table below.
Error indications
OPERATION
TIMER lamp
lamp (green)
(orange)
(1)
(2)
(1)
(4)
(1)
(6)
(2)
(6)
(2)
(9)
(3)
(1)
(3)
(2)
(3)
(10)
(4)
(1)
(4)
(2)
(5)
(1)
(5)
(2)
(5)
(3)
(9)
(15)
(13)
(1)
Display mode
: 0.5s ON / 0.5s OFF
BOX
: 0.1s ON / 0.1s OFF
( ) : Number of fl ashing
Wired Remote
Controller Error
Error contents
FILTER lamp
code
(red)
Remote controller
communication error
Network communication
error
Peripheral device
communication error
Address setting error
Connection unit number
error in wired remote
controller system
Indoor unit power supply
abnormal
Indoor unit main PCB
error
Indoor unit
communication circuit
(wired remote controller)
error
Room temp. sensor error
Indoor unit Heat Ex.
sensor error
Indoor unit fan motor1
error
Coil (Expansion value)
error
Water Drain Abnormal
Outdoor unit error
RB unit error
En-16
7/12/2012 11:16:19 AM
7/12/2012 11:16:19 AM