The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that
it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components must not
venting
be combined.
EN
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20
feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two
horizontally or three vertically (excluding the appliance and the air terminal connections) when using fl exible venting.
Horizontal runs may have a 0" rise per foot or 0mm rise per meter however for optimum performance it is recommended
that all horizontal runs have a minimum 1/4" rise per foot or 21mm rise per meter using fl exible venting. For safe and proper
operation of the appliance, follow the venting instructions exactly.
A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings
and serves both dwellings. Local codes or regulations may require different clearances.
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼" (31.8mm) air gap
all around between the inner liner and outer liner is required for safe operation.
2.1
typical vent installation
If approved for use with a power vent kit, state: "This appliance is certifi ed for use with a
WARNING
!
power vent kit. Contact your local authorized dealer for more information."
If not, cover with a white box.
•
The first 2 feet of outer 7" (187mm) diameter vent pipe from the appliance must be wrapped in the 1" (25mm)
thick insulation sleeve (supplied). Make sure the insulation is pulled down tight to the appliance when installed.
Thereafter, a 2" (51mm) clearance all around the vent pipe from combustible materials on all horizontal vent
sections is required.
10" (254mm)
MINIMUM
46"
(1168mm)
When venting, the horizontal run must be kept to a maximum of 20 feet (6m). If a 20 foot (6m) horizontal run is
required, the appliance must have a minimum vertical rise immediately off the appliance of 57" (1448mm). When
terminating vertically, the vertical rise is a minimum 3 feet (1m) and a maximum 40 feet (12m) above the appliance.
* First two feet (0.6m) requires insulation sleeve
10
W415-2358 / B / 05.17.22
DRAFT
* FIRST TWO
24" (610mm)
MAXIMUM
INSULATION
56"
(1422mm)
PLUS RISE
FEET
REQUIRES
SLEEVE
46"
(1168mm)
DRAFT
16" (406mm)
MINIMUM
3 FEET (1m)
MINIMUM
40 FEET (12m)
MAXIMUM
45.6A