1. Drill a hole through each of the measurements/locations you marked in the Preparation for Wall
2. Clean the holes with a wire brush.
3. Make sure the head of the bolt is flush with the top threaded part of the anchor then insert the
4. Push anchor assembly until washer is snug against the wall.
5. Tighten each bolt with a wrench (use a screwdriver for flat/round heads), approximately three
6. Back the bolts out sufficiently to allow them and their washers to engage the top center of one
2.3.3.4.

Wall Mounting, Wood Surface

When mounting the IND780 to a wooden wall or similar surface, use four #12 screws of at least 1
1/4" (30 mm) length, each with a flat washer of minimum 1/2" (12 mm) diameter.
Install the screw and washer, leaving sufficient gap to accommodate the slotted hole in the bracket
– see Figure 2-9 and Figure 2-11.
Periodically inspect the terminal to insure that it is securely anchored to the wall. If not, remove the
terminal and retighten the mounting anchor bolts.
2.3.3.5.

Positioning Terminal on Fasteners

Place the holes in the terminal brackets over the fasteners, and slide the terminal down firmly so
that each fastener and washer engages the slots in the bracket (see Figure 2-9).
For wallboard or drywall mounting, after engaging the brackets pull them away from the wall until
the toggle nuts are felt to contact the inside of the wall. If necessary, unmount the terminal and
tighten the bolts slightly. Figure 2-14 shows the relationship between bracket, hardware and wall.
2-10
METTLER TOLEDO IND780 Installation Guide
Figure 2-13: Sample Mounting Hardware, Concrete or Cement
Mounting section. Use a carbide bit conforming to ANSI B94, 12-77 with the same size bit as
anchor diameter (typically 5/16" (8 mm)). The depth of the hole should be deeper than 1/2"
(12 mm).
anchor assembly through the mounting holes and into the base material.
or four full turns or until anchor is tightly secured to the base material.
of the slotted holes in the mounting brackets (see Figure 2-9 and Figure 2-11).
Figure 2-14: Wallboard or Drywall Installation