Technical Data
6.2.3
Flow direction above seat
The valve is closed by spring force (control function A, CFA) with
the medium flow. As the medium pressure is over the swivel plate, it
supports the closing process of the valve and also contributes to the
sealing of the valve seat. The valve is opened by the pilot pressure.
WARNING!
Risk of injury from water hammer!
A water hammer could crack the lines and device. Due to the risk of
water hammer, valves with a flow direction above seat must not
be used for liquid media.
▶ Consider the type of flow direction and the type of medium for
operation of the device.
To ensure complete opening, the minimum pilot pressure
must be applied.
Fig. 3:
Flow direction above seat (closing with medium)
Type 2012
7
TECHNICAL DATA
7.1
Conformity
The globe control valve Type 2012 conforms with the EC Directives
according to the EC Declaration of Conformity.
7.2
Standards
The applied standards, which verify conformity with the EC Directives,
can be found on the EC-Type Examination Certificate and / or the EC
Declaration of Conformity.
7.3
Type label
Orifice
Control function
Type
2012 A 32,0 PTFE VA
G 1/4 P med 15 bar
Pilot 5 - 10 bar
00182076
Id. Number
Operating pressure
Connection type, Nominal pressure
Fig. 4:
Description of type label
english
Seal material
Body material
W1X LU