If, for example, the pump is blocked due to water supply failure, the inverter automatically starts a test procedure to
verify that the unit is effectively without water permanently. During the sequence of operations, if a reset attempt
succeeds (for example water has returned), the procedure is interrupted and normal operation is resumed.
Table 32 shows the sequence of operations performed by the inverter for the different types of block.
Display message
BL
LP
HP
OT
OB
OC
OF
8 RESET AND FACTORY SETTINGS
8.1 General system reset
To reset the system, hold down the 4 keys simultaneously for 2 sec. This operation is the same as disconnecting the
power, waiting for it to close down completely and supplying power again. The reset does not delete the settings
saved by the user.
8.2 Factory settings
The device leaves the factory with a series of preset parameters which may be changed according to the user's
requirements. Each change of the settings is automatically saved in the memory and, if desired, it is always possible
to restore the factory conditions (see Restoring the factory settings par 8.3 – Restoring the factory settings).
8.3 Restoring the factory settings
To restore the factory values, switch off the device, wait until the display has switched off completely, press and hold
down the "SET" and "+" keys and turn on the power; release the two keys only when the letters "EE" appear.
This restores the factory settings (a message and a rereading on EEPROM of the factory settings permanently saved
in the FLASH memory).
Once all the parameters have been set, the device returns to normal operation.
NOTE: Once the factory values have been restored it will be necessary to reset all the parameters that characterise
the system (gains, setpoint pressure, etc.) as at the first installation.
Automatic reset of error conditions
Description
Block due to water failure
Block due to low line voltage - Reset when specified voltage is restored
Block due to high internal
power supply voltage
Block due to overheating of
final power stages
(TE > 100°C)
Block due to overheating of
printed circuit
(BT> 120°C)
Block due to current
overload on electric pump
motor
Block due to current
overload on final stages of
output

Table 32: Auto-reset of blocks

ENGLISH
Automatic reset sequence
- One attempt every 10 minutes for a total of 6 attempts
- One attempt every hour for a total of 24 attempts
- One attempt every 24 hours
- Reset when voltage returns to a specified value
- Reset when temperature of final power stages falls below 85°C
- Reset when temperature of printed circuit falls below 100°C
‐ An
attempt every 10 minutes for a total of 6 attempts
- An attempt every hour for a total of 24 attempts
- One attempt every 24 hours
- An attempt every 10 minutes for a total of 6 attempts
- An attempt every hour for a total of 24 attempts
- One attempt every 24 hours
94