Parameter Setting Block Via Password; Enabling And Disabling The Motor; Table 15: Error Status Messages On Main Page; Table 16: Status Bar Indications - DAB ACTIVE DRIVER PLUS M/T 1.0 Instructions D'utilisation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 100
BP1
BP2
NC
F1
F3
F4
P1
P2
P3
Com. icon with
number
Com. icon with E
Ei
Vi
EY
EE
No power supply Warning due to power supply voltage failure
The other menu pages vary according to the associated functions, and are described below according to the type of
specification or setting. After entering any one of the menus, the lower section of the page always shows a summary
of the main operating parameters (operating status or possible fault status, applied frequency and pressure).
This enables a constant overview of the main machine parameters.
Identifier
GO
SB
FAULT
The following can be shown on parameter display pages: numerical values and unit of measurement of current item,
values of other parameters related to setting of current item, graphic bar, lists; see Figure 12.
To preserve the screen, the page displayed disappears 10 min after the last key was pressed and the screensaver is
shown. The screensaver switches off all the display pixels and an algorithm lights them in random order.

3.4 Parameter setting block via Password

The inverter is equipped with a password protection system. If a password is set, the inverter parameters will be
accessible and visible, but it will not be possible to change them, except the parameters SP, P1, P2, P3, RP, FP, LA,
CT, MS.
In turn, the parameters SP, P1, P2, P3 are limited by SX (SX is subordinate to the password). The password
management system is located in the menu "technical assistance" and is managed by means of parameter PW, see
paragrap 6.6.20 .

3.5 Enabling and disabling the motor

Once the first configuration has been performed with the wizard, the [RUN/STOP] key can be used to disable and re-
enable the motor control. When the [RUN/STOP] key is pressed, the display shows the icon of the key pressed and
the icon changes its appearance when the disabled/enabled status changes. If the inverter is running (green led ON
yellow led ON) or is stopped (green led OFF yellow led ON), the motor control can be disabled by pressing the
[RUN/STOP] key for 2 s.
Blockage due to reading error on the internal pressure sensor
Blockage due to reading error on the remote pressure sensor
Pump not connected
Float function status/alarm
System disable function status/alarm
Low pressure signal function status/alarm
Operating status with auxiliary 1 pressure
Operating status with auxiliary 2 pressure
Operating status with auxiliary 3 pressure
Operating status in multi inverter communication with specified address
Error status in communication of multi inverter system
Blockage due to i-th internal error
Blockage due to i-th internal voltage out of tolerance
Block for cyclicality abnormal detected on the system
Writing and rereading on EEPROM of the factory settings

Table 15: Error status messages on main page

Figure 12: Menu parameter display

Status bar indications at the bottom of each page
Electric pump ON. In case of no flow, the indicator blinks.
Electric pump OFF
Presence of error that prevents control of the electric pump

Table 16: Status bar indications

ENGLISH
Description
72

Publicité

Table des Matières
loading