Input Data
MPP voltage range
Input voltage range (at 1000 W/m² / 14°F in an open circuit)
Max. input current (MPP1/MPP2)
Max. short circuit current of solar modules (I
4)
Max. recovery current
Output Data
Nominal output power (P
Max. output power
Phases
Nominal grid voltage
AC voltage operating range
Adjustment range for grid voltage
Nominal output current
Maximum output current
Nominal frequency
Total harmonic distortion
Power factor (cos phi)
General Data
Maximum efficiency
CEC efficiency
Cooling
Protection class
Dimensions h x w x d
Weight (full/lite version)
Permissible ambient temperature
Permissible storage temperature
Permissible humidity
Protection Devices
Reverse polarity protection
Islanding protection
Arc detection/interruption
PV insulation monitoring
Overtemperature
58
SC PV
)
nom
) (MPP1/MPP2)
at 440 V
at 480 V
at 440 V
at 480 V
at 440 V
at 480 V
at 440 V
at 480 V
20.0-3 480
450–800 V DC
200–1000 V DC
33.0/25.0 A
49.5/37.5 A
49.5/37.5 A (RMS)
20000 W
20000 W
3 ~ NPE
254 V / 440 V
277 V / 480 V
-12 ... +10%
127–322 V / 220–558 V
26.2 A
24.1 A
29.8 A
27.4 A
50 / 60 Hz
< 3.5%
0 - 1 ind./cap.
98.00%
97.00%
Controlled forced-air ventilation
NEMA 4X
28.5 x 20.1 x 8.9 in.
725 x 510 x 225 mm
95.7 / 95.0 lbs. (43.4 / 43.1 kg)
-40°F ... +140°F (-40°C ... +60°C)
-40°F ... +158°F (-40°C ... +70°C)
0–100%
Integrated
Integrated
Integrated
Integrated
Operating point shift /
active cooling
22.7-3 480
500–800 V DC
5)
22727 W
22727 W
29.8 A
27.3 A
33.8 A
31.1 A
1)
2)
97.50%

Publicité