Connection of safety emitter-receiver photocells in closing (SG.C)
Connection of safety emitter-receiver photocells in opening (SG.A)
Connection to the grid
We recommend installing opening and closing
safety photocells.
1 Complete the connections as shown in the figure.
2 Duly programme the actuator:
Closing photocells with testing: C511
Closing photocells without testing: C510
Without closing photocells: C500
For further details on programming, see "Start up
and programming" on page 54.
We recommend installing opening and closing
safety photocells.
1 Complete the connections as shown in the figure.
2 Duly programme the actuator:
Opening photocells with testing: C411
Opening photocells without testing: C410
Without opening photocells: C400
For further details on programming, see "Start up
and programming" on page 54.
1 Connect the line cable (L) to the connection strip
lower terminal and the neutral cable (N) to the
upper terminal.
2 Connect the earth cable (T) to the actuator frame.
3 Ensure the general cut-out (F) is correctly in place.
Cut-out (LIS424 - LIS624): FUS 5x20, 2.5A
Cut-out (LIS424M - LIS624M): FUS 5x20, 4A
Never forget to connect the earth cable, in
order to prevent the risk of electrical discharge.
INSTALLATION
LINCE actuator for sliding gates
53