7.3.6 External default set-value (C.02)

è For external default set-values, enter a scale limit within the selected
temperature range.
The temperature range corresponding to the standard signal (4-20 mA) must be
set up, i.e., enter the temperature at 4 mA (lower limit) and 20 mA (upper limit).
Example:
7.3.6.1
Lower limit value
è Limit the lowest control range using the lower limit value
NOTE
With external set-values (standard signals) the error message
E.02 appears as soon as a signal less than 4 mA is read in.
Setting the pre-comma value of the lower limit value
Setting the post-comma value of the lower limit value
38
Temperature range 14 (0 to 100 °C; 32 to 212 °F)
Lower limit value
Upper limit value
20 °C (68 °F)
60 °C (140 °F)
Increase of the pre-comma value
Proceed to set the post-comma
value
Increase of the post-comma value
Continue from 7.3.6.2
4 mA
20 mA
Type 8625