GB
Technical data at 25 °C/77 °F
1)
The design of the inverter prevents it from causing DC leakage current.
9.2
AC cables and line circuit breakers
Conductor cross-sections of the AC cables and suitable line circuit breakers
Inverter
StecaGrid 1800
2) 3)
StecaGrid 2300
2) 3)
StecaGrid 3000
2)
StecaGrid 3010
2) 3)
StecaGrid 3600
2) 3)
StecaGrid 4200
2) 3)
1)
Power loss of the AC cables at the rated power of the inverter and a cable length of 10 m
2)
coolcept
3)
coolcept-x
132
StecaGrid 3000
coolcept
CE symbol, VDE AR N 4105, G83,
UTE C 15-712-1, AS4777, CEI 0-21
coolcept-x
AC cable conductor
cross-section
1.5 mm²
2.5 mm²
4.0 mm²
1.5 mm²
2.5 mm²
4.0 mm²
1.5 mm²
2.5 mm²
4.0 mm²
1.5 mm²
2.5 mm²
4.0 mm²
2.5 mm²
4.0 mm²
2.5 mm²
4.0 mm²
StecaGrid 3600/-x
CE symbol, VDE AR N 4105, G83
under preparation: AS4777, CEI 0-21
1)
Power loss
24 W
15 W
9 W
31 W
19 W
12 W
40 W
24 W
15 W
40 W
24 W
15 W
37 W
23 W
49 W
31 W
StecaGrid 4200/-x
CE symbol, VDE AR
N 4105, G83, CEI
0-21
Line circuit breaker
B16
B16
B16
B16
B16
B16
B16
B16 or B25
B16 or B25
B16
B16 or B25
B16 or B25
B25
B25
B25
B25
747.431