further instructions:
▶ The user must ensure that the appliance is used in Zone 1/21 or
2/22 only.
▶ The control unit may restrict use in an explosive atmosphere. Follow
operating instructions for control unit.
▶ Check that any cleaning agents are approved for use in explosive
atmospheres.
3.1.2. Media temperature
Danger!
▶ If explosive media are used this can cause additional explosion risks.
▶ If media temperatures are used between 130 °C and 150 °C, the
temperature class T3 / 200 °C applies (dust).
Media temperature
3.1.3. Marking ex area
ptB 13 ateX d103 X
ii 2g c iic t4
ii 2d c t135°c
Warning: not valid when non-ex devices added.
do not open actuator. spring loaded cover.
Fig. 1:
Marking Ex area
8
max. 130 °C
english
Type 2036
Basicsafetyinstructions
The Ex marking is not valid if Non-Ex devices are added.
3.2.
special conditions
To ensure potential equalization, ground the valve body to the
pipe system using an electrically conductive connection.
Danger!
danger of explosion caused by electrostatic charge.
In the event of a sudden discharge from electrostatically charged
devices or individuals there is a risk of an explosion in the Ex area.
▶ Implement suitable measures to ensure that there are no
electrostatically charges in the Ex area (see also "3.1. Use in Ex
area").
▶ Clean the device surface by gently wiping it with a damp or anti-
static cloth only.
▶ Earth the actuator and valve body.
▶ If a plastic body is used, earth the actuator separately.
Ambient temperature range: 0 °C ≤ Tamb ≤ 60 °C