Cross Section Of The Cables; Connections - Gtec SATURN Série Manuel D'installation

Masquer les pouces Voir aussi pour SATURN Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

C
S
ROSS
ECTION OF THE
The manufacturer recommends that the INPUT/OUTPUT and BATTERY cables pass under the UPS unit.
Please refer to the following table for the minimum cross-sections to be used for the input and output cables.
INPUT
mains /
separate bypass (optional)
kVA
PE
L1
10
10
10
12
16
16
15
16
16
20
25
25
*
The cross-sections indicated in the table refer to a maximum cable length of 10 metres.
** The maximum length of the cables for connection to the optional Battery Box is 3 metres.
Note: the maximum cable size that can be inserted in the INPUT, BYPASS and OUTPUT terminal boards is 25mm
cables with cable lugs and 35mm
The maximum section for cables that can be inserted in the BATT terminal board is 10 mm
16 mm
2 for
stripped cables.
C
ONNECTIONS
The very first connection must be the protection conductor or the earth cable which should be
inserted in the terminal marked PE. The UPS must be earthed before use.
Connect the input and output cables to the terminal board as shown in the figure below.
THE INPUT NEUTRAL MUST ALWAYS BE CONNECTED
Note: connections to the BATTERY module are only required when the optional Battery Box is present.
C
ABLES
Cable sizes (mm
L2/L3
N
PE
2.5
10
10
4
16
16
4
16
16
6
25
25
2
for rigid cables.
2
) *
OUTPUT
L
N
10
10
16
16
16
16
25
25
- 78 -
BATTERY** (optional)
PE
+/-
N
4
4
4
6
6
6
6
6
6
10
10
10
2
for cables with cable lugs and
2
for

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Saturn 10 kvaSaturn 12 kvaSaturn 15 kvaSaturn 20 kva

Table des Matières