AS400 P
ORT
PIN #
NAME
1
15V
15
GND
2
REMOTE ON
8
REMOTE OFF
REMOTE
7
BYPASS
4,5,12
BATTERY LOW
BATTERY
6,13,14
WORKING
9,10
LOCK
3,11
BYPASS
N.B.: The figure shows the contacts present inside the UPS, capable of carrying a max. current of 0.5A to 42Vdc.
The position of the contacts shown in the figure is with no alarm or signal present.
(1)
The output may be programmed using the configuration software.
The function indicated is selected by default (factory setting)
AS400 PORT
TYPE
POWER
Isolated auxiliary power supply, +15V±5% 80mA max
Ground to which the isolated auxiliary power supply (15V)
POWER
and the remote commands (Remote ON, Remote BYPASS,
When pin 2 is connected to pin 15 for at least 3 seconds, the
INPUT #1
When pin 8 is connected to pin 15, the UPS is powered off
INPUT #2
When pin 7 is connected to pin 15, the power supply of the
load switches from inverter to bypass. For as long as the
connection remains, the UPS continues to operate from the
bypass even if the input mains voltage is shut off. If the
INPUT #3
jumper is removed when the mains voltage is present, the
UPS resumes operation from the inverter. If the jumper is
removed when there is no mains voltage present, the UPS
Indicates that the batteries are about to run out when
OUTPUT #1
Indicates that the UPS is running on battery power when
OUTPUT #2
When the contact is closed, indicates that the UPS is
OUTPUT #3
When the contact is closed, indicates that the load is
OUTPUT #4
- 99 -
FUNCTION
Remote OFF) refer
UPS is turned on
instantly
resumes operation from the battery
contact 5/12 is closed
contact 6/14 is closed
(1)
locked
powered via the bypass
(1)
(1)
(1)