Wilo VeroLine-IP-E Série Notice De Montage Et De Mise En Service page 109

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Classification No.
Electronics
E070
errors
E071
E072
E073
E075
E076
E077
E078
E096
E097
E098
E121
E122
E124
Impermissi-
E099
ble combina-
torics
Tab. 10: Error table
Additional explanations of error
codes
Installation and operating instructions Wilo-VeroLine-IP-E, VeroTwin-DP-E
Fault
Cause
Internal communica-
Internal electronics error
tion error (SPI)
EEPROM error
Internal electronics error
Power section/fre-
Internal electronics error
quency converter
Impermissible elec-
Internal electronics error
tronic module number
Charging relay defec-
Internal electronics error
tive
Internal transformer
Internal electronics error
defective
24 V operating voltage
Differential pressure sen-
for differential pres-
sor defective or con-
sure sensor defective
nected incorrectly
Impermissible motor
Internal electronics error
number
Infobyte not set
Internal electronics error
FlexPump data record
Internal electronics error
missing
FlexPump data record
Internal electronics error
invalid
Motor PTC short-cir-
Internal electronics error
cuit
Interruption to NTC
Internal electronics error
power element
Interruption to NTC
Internal electronics error
electronic module
Pump type
Different pump types
have been intercon-
nected
Error E021:
Error 'E021' indicates that the pump requires more power than is per-
mitted. To ensure that the motor and electronic module do not suffer
irreparable damage, the drive protects itself by switching the pump
off if an overload lasts more than 1 minute.
The most common causes of this error are a pump that is configured
too small, especially when pumping viscous fluids, or an excessive
volume flow in the system.
When this error code is displayed, there is not an error in the electronic
module.
Error E070; possibly combined with error E073:
If additional signal lines or control lines are connected to the electronic
module, the effects of EMC (immission/interference resistance) may
interrupt communication. This results in error code E070 being displayed.
You can check this by disconnecting all the communication lines
installed by the customer from the electronic module. If the error no
longer occurs, there could be an external interfering signal on the
communication line(s) that exceeds the applicable standard values.
The pump can only return to normal operation once the source of
interference is remedied.
Remedy
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Check differential pressure
sensor connection
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
Request customer service
English
Error type
HV
AC
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
103

Publicité

Table des Matières
loading

Table des Matières