D
22
→
Tighten the duplication
system "D" until free contact
is obtained with the top of
the limiter, using a flat No 27
spanner.
→
Fully tighten the duplication
rod on the actuator rod using
a screwdriver with a blade of
suitable size.
→
Depressurize the actuator of a
valve which is normally closed
(function "A") or has a double
effect (function "I"): the valve
recovers its default position.
english
Type 1062
Assembly
→
Insert the position feedback
housing into the duplication
system "D" setting the
cable gland in the direction
desired and making sure, on
a mechanical contact version,
that you do not damage the
C
contact levers on the switches.
D
→
Fasten the housing and the
duplication system by tight-
ening the cone point set screw
"C" using a hexagonal male
spanner.
→
Unscrew the cover "Q" on the
position feedback.
→
Unscrew the cable gland "R".
→
Thread the cable through the
Q
cable gland.
→
Wire according to the wiring
diagram for your version of the
1062: See chap. „8 Installation
and wiring".
→
Fasten the cable gland to
ensure tightness of the product.
R