Important Safety Notes - HYDAC ELECTRONIC ENS 3000 Notice D'utilisation

Masquer les pouces Voir aussi pour ENS 3000:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ENS 3000 IO-Link
4.3

IMPORTANT SAFETY NOTES

Additional installation suggestions which, from experience, reduce the effect of
electromagnetic interference:
• Make line connections as short as possible
• Use shielded lines (e.g. LIYCY 4 x 0.5 mm²)
• The cable shielding must be fitted by qualified personnel, subject to the ambient
conditions and with the aim of suppressing interference.
• Keep the instrument well away from the electrical supply lines of power equipment, as
well as from any electrical or electronic equipment causing interference.
• Always connect the earthing screw of the ENS 3000 to the earthing rail (e.g. in the
control cabinet). We recommend using a cable with a diameter of 1 mm² and as short
a line length as possible.
The level switch ENS 3000 should be mounted vertically inside the tank. If not mounted
vertically, the accuracy of the ENS may decrease with increasing tilt angle (additional
inaccuracy at a tilt angle of 5°: approx. ±0.5%; additional inaccuracy at a tilt angle of 10°:
approx. ±1.5%).
CAUTION!
The ENS 3000 electronic level switch is not suitable for operation at pressures
exceeding atmospheric pressure. Short-term peak pressures up to 3 bar, however,
may be possible and will not cause damage to the device if not exceeding 1 minute
of time.
Version 2014/12/11
Earth contact M3
(earthing screw M3 and toothed
washer M3 included)
HYDAC ELECTRONIC GMBH
page 9
Part No. 669898

Publicité

Table des Matières
loading

Table des Matières