Table 1
Min floor area (A
m
c
(Kg)
1.2
1.3
1.4
1.5
1.84
7.20
6.15
5.71
5.33
2.0
8.51
7.25
6.25
5.79
2.2
10.30
8.77
7.57
6.59
2.4
12.26 10.44
9.00
7.84
2.6
14.38 12.26 10.57
9.21
2.8
16.68 14.21 12.26 10.68
3.0
19.15 16.32 14.07 12.26 10.77
3.2
21.79 18.56 16.01 13.94 12.26 10.86
3.4
24.6
20.96 18.07 15.74 13.84 12.26 10.93
3.6
27.58 23.50 20.26 17.65 15.51 13.74 12.26
3.8
30.72 26.18 22.57 19.66 17.28 15.31 13.66 12.26
4.0
34.04 29.01 25.01 21.79 19.15 16.96 15.13 13.58
Table 2 (Examples)
Minimum opening for natural ventilation A
(dm
m
(Kg)
Room A area (m
c
7
10
13
1.84
-
-
2.0
0.10
-
2.2
0.67
-
2.4
1.24
0.16
2.6
1.81
0.79
2.8
2.38
1.41
0.41
3.0
2.95
2.03
1.08
3.2
3.52
2.66
1.74
3.4
4.09
3.28
2.41
3.6
4.66
3.90
3.07
3.8
5.23
4.53
3.74
4.0
5.80
5.15
4.40
Minimum opening for natural ventilation A
(dm
mc (Kg)
Room A area (m
7
10
13
1.84
-
-
2.0
-
-
2.2
-
-
2.4
0.36
-
2.6
0.89
-
2.8
1.42
0.27
3.0
1.95
0.85
3.2
2.48
1.43
0.35
3.4
3.01
2.01
0.97
3.6
3.54
2.59
1.59
3.8
4.07
3.17
2.21
4.0
4.60
3.75
2.83
PMML0666 rev.0 - 09/2024 - 1000017439
) (m
)
2
min
H
0
1.6
1.7
1.8
1.9
4.99
4.70
4.44
4.21
5.43
5.11
4.82
4.57
5.97
5.62
5.31
5.03
6.89
6.13
5.79
5.48
8.09
7.17
6.39
5.94
9.38
8.31
7.41
6.65
9.54
8.51
7.64
9.68
8.69
9.81
11.0
nvmin1
) h
=1.3 m
2
0
)
2
15
18
20
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.43
-
-
1.12
0.18
-
1.81
0.90
0.30
2.50
1.63
1.04
3.19
2.35
1.78
3.88
3.07
2.52
nvmin1
) h
=1.5 m
2
0
)
2
15
18
20
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.27
-
-
0.91
-
-
1.55
0.56
-
2.19
1.23
0.59
Minimum opening for natural ventilation A
(dm
m
(Kg)
Room A area (m
c
7
10
13
1.84
-
-
2.0
-
-
2.2
-
-
2.4
-
-
2.6
0.08
-
2.8
0.58
-
3.0
1.08
-
3.2
1.57
0.36
3.4
2.07
0.90
3.6
2.57
1.45
0.29
3.8
3.07
1.99
0.87
4.0
3.57
2.54
1.46
NOTE
The minimum opening area for natural ventilation between room A
and room B is calculated by the following formula:
A
= 1.51 x (m
-m
nv,min1
max
c
m
= 0.571 x h
x (A
max
0
roomA
Where:
• A
:minimum opening for natural ventilation
nv,min1
between room A and room B, in dm
• A
: room A area, in m
2
roomA
• m
: the allowable maximum refrigerant charge in the
max
room A, in kg.
• Mark "-" in the above table indicates that the room A is
large enough for installation without adjacent room B.
• For intermediate refrigerant charges, room A area
and installation height, select the higher charge
value, the smaller room area and the lower height
value to choose the A
nv,min1
refrigerant charge is 2.9 kg, room A area is 8 m
the installation height is 1.85 m, then A
according to the table (h
0
3.2 Service space
H: 1200~1500 mm
Recommended unit height for proper access to the control unit
panel (Unit controller).
h: 350 mm
Minimum unit height for installing the shut-off valves and the first
bending pipe line.
nvmin1
) h
=1.7 m
2
0
)
2
15
18
20
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.12
-
-
0.73
-
-
) x (A
/m
)
˄(1/2)
roomA
max
)
˄(1/2)
.
2
.
. For example, if the
and
2
=1.08 dm
nv,min1
=1.7 m)
Units in mm.
2
EN