5. Switch on the battery or the load-break switch of the battery (see documentation of the battery
manufacturer).
☑ All 3 LEDs light up. The start-up phase begins.
☑ All 3 LEDs go out again after approximately 90 seconds.
☑ Depending on the available power, the green LED pulses or is continuously illuminated.
The inverter is feeding in.
6. If the LEDs do not start to glow, the ribbon cable between the assembly in the enclosure lid
and the communication assembly in the inverter is most likely not properly plugged in. Ensure
that the ribbon cable is securely plugged into the sockets at both ends.
7. If the green LED is still flashing, the conditions for activating feed-in operation are not yet met.
As soon as the conditions for feed-in operation are met, the inverter starts with feed-in
operation and, depending on the available power, the green LED will light up continuously or
it will pulse.
8. If the red LED lights up, an error has occurred. Rectify the error (for information regarding
troubleshooting see the user manual under www.SMA-Solar.com).
7.3
Establishing a connection to the user interface
7.3.1
Establishing a Direct Connection via Ethernet
Requirements:
☐ The product must be commissioned.
☐ A smart device (e.g. laptop) with an Ethernet interface must be available.
☐ The product must be connected directly to the smart device.
☐ The respective latest version of one of the following web browsers must be installed on the
smart device: Chrome, Edge, Firefox or Safari.
☐ The installer's SMA Grid Guard code must be available to change network-relevant settings
after the first 10 hours of feed-in operation, or after completing the installation assistant. You
can request the SMA Grid Guard code via the Online Service Center.
☐ JavaScript must be enabled in the web browser of the smart device.
IP address of the inverter
• Standard inverter IP address for the direct connection via Ethernet: 169.254.12.3
Procedure:
1. Open the web browser of your smart device and enter the IP address 169.254.12.3 in the
address bar.
Web browser displays warning
2.
After the access address of the product has been entered, a message might appear
indicating that the connection to the user interface of the product is not secure.
• Continue loading the user interface (scroll to bottom and click proceed/advance).
☑ The login page of the user interface opens.
Installation Manual
7 Commissioning
SBSxx-US-10-IA-xx-14
59